- BrandЭлеватормельмаш
- Country of manufactureRussia
Three - pass horizontal fire - tube steam boilers are designed to produce steam with a temperature of no more than 120 ° C (due to the built - in superheater with an overpressure of up to 0.07 MPa (0.7 kg / cm2) for the purpose of heat supply of technological processes in the production of: concrete goods, for steam heating, for steaming chambers, in the construction industry, in the food industry, in the production of corrugated cardboard, in the oil and gas industry, agriculture, for heat treatment of feed, pasteurization of milk, in the utilities, food and woodworking industries.
Specifications
The main parameters and dimensions of three - pass horizontal fire - tube steam boilers are shown in the table:
No. | The name of indicators | Brand | |||||
KPa - 0.3 LV | KPa - 0.7 LV | KPa - 0.9 LV | KPa - 0.3 Gn | KPa - 0.7 Gn | KPa - 0.9 Gn | ||
1 | A type | stationary, horizontal, three - way, fire - tube | |||||
2 | Supply voltage | 50 Hz 220 or 380V * | |||||
3 | Steam capacity for normal steam, not less, kg / hour | 300 | 700 | 900 | 300 | 700 | 900 |
4 | Thermal power of the burner, MW, not less | 0.34 | 0.6 | 0.8 | 0.34 | 0.6 | 0.8 |
- consumption of natural gas m 3 / hour, no more | - | 37 | 80 | 90 | |||
- consumption of liquid furnace fuel kg / hour, no more | thirty | 63 | 85 | - | |||
five | Fuel used | liquid, oven | low pressure natural gas | ||||
6 | Exit to operating mode, min. , No more | 25 | 25 | 25 | thirty | thirty | thirty |
7 | Steam parameters: | - | |||||
- working pressure, MPa | 0.02 - 0.06 | ||||||
- permissible excess pressure, no more, MPa | 0.07 | ||||||
- Temperature of superheated steam, no more, ° С | 120 | ||||||
eight | Heating surface, m 2 | 16.5 | 20.2 | 22.9 | 16.5 | 20.2 | 22.9 |
nine | Overall dimensions, mm. , No more | - | |||||
- length (without burner) | 1780 | 2210 | 2555 | 1780 | 2210 | 2555 | |
- width (with frame and remote control) | 1925 | 1925 | 1925 | 1925 | 1925 | 1925 | |
- height (without chimney) | 2270 | 2270 | 2270 | 2270 | 2270 | 2270 | |
ten | Boiler weight, no more, kg (without mounting parts) | 1410 | 1530 | 1700 | 1410 | 1530 | 1700 |
eleven | Service life, years, not less | 6 | |||||
12 | Safety valve, pcs | 2 | |||||
13 | Number of explosive valves, pcs | 1 | |||||
fourteen | Gas pressure control sensor, pcs | - | 1 pressure gauge | ||||
fifteen | Gauge column type | electrode (3 electrodes) | |||||
sixteen | Working and emergency pressure sensor | Electrical contact pressure gauge | |||||
17 | Efficiency, not less than% | 90 | 92 | ||||
18 | The noise level at the workplace does not exceed dBA | 75 | |||||
nineteen | Total installed power, kW, not more | 4.1 | |||||
20 | Feed water requirement: | - | |||||
- suspended matter, mg / l, no more | five | ||||||
- transparency "along the ring", cm | 50 | ||||||
- total hardness, mg. eq / l, no more | five | ||||||
- carbonate hardness, mg eq / l, no more | 3 | ||||||
- iron content, mg / l, no more | 0.1 | ||||||
- oxygen content, mg / l, no more | 0.03 | ||||||
- Н, pH units, no more | eight |
* Depending on the boiler configuration
Product structure and delivery set
The boiler consists of:
- drum;
- front cover;
- back cover;
- burners;
- water treatment unit with make - up pumps;
- level sensor;
- control box;
- safety valves;
- steam collector;
- level indicator;
- instrument panel;
- frames with supports.
The technological process of vaporization is as follows:
Flue gases passing through the gas path of the boiler heat up its heat exchange surfaces. Water entering through the water treatment unit enters the boiler, where it is heated by heat exchange surfaces and evaporates. The steam passing through the superheater is superheated by the flue gases and goes to the consumer. The slags formed during the evaporation of water are periodically removed from the boiler by blowing. Boiler control and control over the technological process of vaporization is carried out using electrical equipment.